LF-FR
APPLICATION
KCW Single core FR-LF wire is environment friendly to the environment & suitable for use where high flexibility is of prime importance. This is also suitable for indoor and outdoor installation in industries, household appliances, power supply for refrigerators, air conditions as well as building electrification.
CABLES DESIGNATION/TYPE
LF-FR
PRODUCT FEATURE
- Flame Retardant
- Smooth & glossy surface with enhanced lubrication properties
- High Insulation Resistance
- ROHS Complaint
DESIGN
- Plain annealed bunched circular copper conductor
- Insulation Flexible PVC compound
APPLICABLE STANDARD
- IS 694 : 2010
- IEC 60332 - 1 : 2004
- ASTM 2863 : ASTM D2803 - 17 a
APPROVALS
- IS 8130 : 2013 BIS
CABLE CHARACTERISTICS
- Nominal Voltage (UO/U) : 600/1100 V
- Max Operating Temperature : 70°C
- Temperature Range : -15°C to +70°C
- Flame Resistance : ASTM D2863
- Flammability : IEC 60332 - 1:2004
- Minimum Bending Radius : 8D
LF-FR
| Normal Area of Conductor SQ.MM. |
Max Diameter Of each strand |
Thickness of Insulation (Nom.) mm. |
Approx. Overall Diameter mm. |
Current Carrying Capacity Rating Amps. | Resistance(Max.) Per Km.@20° Ohms |
| **0.75 | 24/0.20 | 0.6 | 2.5 | 7 | 26 |
| *1 | 14/0.30 | 0.7 | 2.8 | 12 | 18.1 |
| *1.5 | 22/0.30 | 0.7 | 3.1 | 16 | 12.1 |
| *2.5 | 36/0.30 | 0.8 | 3.8 | 22 | 7.41 |
| **4 | 56/0.30 | 0.8 | 4.4 | 29 | 4.95 |
| **6 | 84/0.30 | 0.8 | 5.2 | 37 | 3.3 |
| **10 | 80/0.40 | 1.0 | 5.8 | 51 | 1.91 |
| **16 | 126/0.40 | 1.0 | 6.8 | 68 | 1.21 |
*Class 2 Conductor As Per IS 8130
**Class 5 Conductor As Per IS 8130
THE ABOVE DATA & IMAGES ARE INDICATIVE AND MAY BE REVISED WITHOUT PRIOR INFORMATION.
"KCW" WILL NOT BE LIABLE FOR ANY DAMAGES ARISING OUT OF INCORRECT APPLICATION OF ITS PRODUCTS.