ZHFR : ZERO HALOGEN FLAME RETARDANT
ZHFR CABLES
ZH-FR represents our dedication to environmental sustainability. This eco-friendly solution, combined with improved safety measures for fire incidents, is designed to mitigate the primary cause of death in indoor fires: smoke inhalation.
In the unfortunate event of a fire, Ban Fire - ZH-FR, crafted from specially developed in-house PVC polymers, minimizes smoke and halogen gas emissions, ensuring the safety of people in residential and commercial spaces, facilitating their rescue.
CONSTRUCTION
Conductor: 99.98% Pure electrolyte grade bright Annealed Bare Copper.
Insulation: ZH-FR PVC compound with a high insulation resistance ensures uninterrupted power supply at all weather conditions.
Operating Temp: -15°C to maximum + 85°C
PROPERTIES
|
Test |
Test Method |
Values |
|
Limited Oxygen Index |
IS 10810 P - 58 |
>29% |
|
Limited Temp. Index |
IS 10810 P - 64 |
>2500 C |
1100 VOLTAGE GRADE FOR INDUSTRIAL APPLICATION
|
Sheath Normal Cross sectional area Of conductor |
Number/ Nom. Dia of Cond. Strands* |
Max. Conductor Resistance per Km at 200C |
Normal Overall Diameter Of Cable |
Normal Thickness Of Insulation |
Current Carrying Capacity 2 Cables Single Phase |
|
|
In Conduit/ Trunking |
Unenclosed Clipped directly to a surface or on cable tray |
|||||
|
Sq.mm. |
mm. |
ohms |
mm. |
mm. |
Amps. |
Amps. |
|
**0.50 |
16/0.20 |
39.00 |
2.20 |
0.6 |
4 |
4 |
|
**0.75 |
24/0.20 |
26.00 |
2.30 |
0.6 |
8 |
8 |
|
*1.00 |
14/0.30 |
18.10 |
2.70 |
0.7 |
12 |
13 |
|
*1.50 |
22/0.30 |
12.10 |
3.00 |
0.7 |
14 |
18 |
|
*2.50 |
36/0.30 |
07.41 |
3.60 |
0.8 |
20 |
24 |
|
**4.00 |
56/0.30 |
04.95 |
4.00 |
0.8 |
26 |
32 |
|
**6.00 |
84/0.30 |
03.30 |
4.60 |
0.8 |
34 |
41 |
|
**10.0 |
140/0.30 |
01.91 |
6.10 |
1.0 |
47 |
58 |
|
**16.0 |
126/0.40 |
01.21 |
7.20 |
1.0 |
65 |
79 |
*Class 2 Conductor As Per IS 8130